Knauf ET Board

ET Board

Description

Knauf Elevated Temperature Board 850° is a lightweight insulation (2.8 PCF, 44.9 kg/m3) made from inorganic glass fibers bonded with a high-temperature thermosetting resin. It is a semi-rigid, board-like form with superior handling properties and insulating effectiveness at minimum cost.

Application

Knauf Elevated Temperature Board 850° is used for boiler walls, hot precipitators, hot ductwork, cylindrical tanks, towers, stacks, and industrial ovens.

Features and Benefits

Excellent Thermal Properties

  • Reduces operating cost.

Low Installed Cost

  • Lightweight.
  • Easy to fabricate.
  • Sizes up to 4' x 10' available.

Polybag and Sleeve Packaging

  • Damage resistant.
  • Reduces storage space.

Resilient Fiber Glass

  • Maintains integrity at elevated temperatures.

Specification Compliance

In U.S.:

  • ASTM C 612; Type IA, IB, II
  • ASTM C 795
  • HH-I-558C (Amend. 3); Form A, Class 1, 2, 3
  • MIL-I-22023D; Type III
  • MIL-I-24244C
  • NRC Reg. Guide 1.36
  • USCG 164.109/15/0

In Canada:

  • CAN/ULC S102-M88
  • T.C.270.F1.315
  • CGSB 51-GP-10M

Technical Data

Surface Burning Characteristics

  • Does not exceed 25 Flame Spread, 50 Smoke Developed when tested in accordance with ASTM E 84, CAN/ULC S102-M88 and UL 723.

Temperature Limitation (ASTM C 411)

  • Up to 850°F (454°C)

Alkalinity (ASTM C 871)

  • Less than 0.6% as Na2O.

Corrosiveness (ASTM C 665)

  • Will not accelerate corrosion of steel.

Resistance to Microbial Growth (ASTM C 1338)

  • No growth.

Application and Specification Guidelines

Precautions

  • During initial heat-up to operating temperatures above 350°F (177°C), a slight odor and some smoke may be given off as a portion of the bonding material used in the insulation begins to undergo a controlled decomposition.
  • If natural convection is not adequate in confined areas, forced ventilation should be provided in order to protect against any harmful fumes and vapors that might be generated.

Storage

  • Protect material from water damage or other abuse. Cartons are not designed for outside storage. Vacuum packaged material can be stored outside if care is taken not to puncture the polybag.

Preparation

  • Apply the product on clean, dry surfaces.

Application

  • All insulation joints must be firmly butted. Mount flush against surfaces to 850°F (454°C) or use in panels mounted away from operating surface.
  • Knauf ET Board 850° is designed to be applied over welded pins and/or studs up to 1/2" (13 mm) in diameter. The board is to be held in place by speed washers, tension clips, or metal mesh reinforcement.
  • Installation method should not compress material beyond maximum 5% at any point.
  • Pins and studs shall be located a maximum of 4" (102 mm) from each edge and spaced no greater than 16" (406 mm) on center.
  • Dual-layer installation with staggered joints is recommended for applications where temperatures meet or exceed 550°F (288°C) and designed thickness is over 3" (76 mm).
  • Finish surface with metal cover, or with insulating cement and canvas.

Caution

Fiber glass may cause temporary skin irritation. Wear long-sleeved, loose-fitting clothing, head covering, gloves, and eye protection when handling and applying material. Wash with soap and warm water after handling. Wash work clothes separately and rinse washer. A disposable mask designed for nuisance type dusts should be used where sensitivity to dust and airborne particles may cause irritation to the nose and throat.

Notes

The chemical and physical properties of Knauf ET Board 850° represent typical average values determined in accordance with accepted test methods. The data is subject to normal manufacturing variations. The data is supplied as a technical service and is subject to change without notice. References to numerical flame spread ratings are not intended to reflect hazards presented by these or any other materials under actual fire conditions. Check with your Knauf regional office to assure information is current.
 
THERMAL EFFICIENCY (ASTM C 177)

Mean

Temperature

Mean

Temperature (SI)

k k (SI)
100°F 38°C .25 .036
200°F 93°C .33 .048
300°F 149°C .40 .058
400°F 204°C .49 .071
500°F 260°C .57 .082
 
FORMS AVAILABLE
Thickness Width Length

1"

(25 mm)

24" and 48"
(610 mm and 1219 mm)
24" to 120"
(610 mm to 3048 mm)

11/2"

(38 mm)

24" and 48"
(610 mm and 1219 mm)
24" to 120"
(610 mm to 3048 mm)

2"

(51 mm)

24" and 48"
(610 mm and 1219 mm)
24" to 120"
(610 mm to 3048 mm)

21/2"

(64 mm)

24" and 48"
(610 mm and 1219 mm)
24" to 120"
(610 mm to 3048 mm)

3"

(76 mm)

24" and 48"
(610 mm and 1219 mm)
24" to 120"
(610 mm to 3048 mm)

31/2"

(89 mm)

24" and 48"
(610 mm and 1219 mm)
24" to 120"
(610 mm to 3048 mm)

4"

(102 mm)

24" and 48"
(610 mm and 1219 mm)
24" to 120"
(610 mm to 3048 mm)

Website Options