Knauf Sonic XP™ Duct Liner with ECOSE® Technology
Description
Knauf Sonic XP™ Duct Liner with ECOSE® Technology is
a flexible, mat-faced insulation bonded with ECOSE Technology. It
is faced with a tightly bonded mat to give the airstream a smooth,
tough surface, resisting damage during installation and operation.
The encapsulant edge coating eliminates airstream flaring.
ECOSE
Technology
ECOSE Technology is a revolutionary
new binder chemistry that makes Knauf Insulation products even more
sustainable than ever. It is based on rapidly renewable bio-based
materials rather than non-renewable petroleum-based chemicals
traditionally used in fiber glass insulation products. ECOSE
Technology reduces binder embodied energy and does not contain
phenol, formaldehyde,acrylics or artificial colors.
Application
Specifically designed as an interior
insulation material for sheet metal ducts used in heating,
ventilating and air conditioning. Provides an optimum combination
of efficient sound absorption, low thermal conductivity and minimal
airstream surface friction.
Features and
Benefits
- Low thermal conductivity.
- Fire-resistant, non-corrosive, durable and resilient.
- Tough, tightly bonded mat
facing.
- Excellent sound absorption.
- Energy conservation.
- Better temperature control.
- Lowers operating costs.
- Greatly reduces noise from fans and
mechanical equipment as well as cross-talk and air movement.
- Withstands damage from normal
handling and shop abuse.
- If necessary, can be cleaned in
accordance with NAIMA’s “Cleaning Fibrous Glass Insulated Air Duct
Systems Recommended Practices.”
- Certified for indoor air quality as a
low emitting product by The GREENGUARD Environmental Institute to
both the GREENGUARD Certification ProgramSM and the more stringent
GREENGUARD Children and SchoolsSM
standard.
- Sustainability:
- Carbon negative: meaning
Knauf insulation products used for thermal insulating purposes
recover the energy that it took to make
them in just hours or a few days, depending on the application.
Once installed, the product continues to save energy and reduce
carbon generation as long as it is in place.
- Fiber glass insulation with ECOSE
Technology contains three primary ingredients:
- Sand, one of the world’s
most abundant and renewable resources
- Post-consumer recycled
bottle glass
- ECOSE Technology which
reduces binder embodied energy by up to 70%
Specification
Compliance
In U.S.:
- ASTM C 1071; Type I
- ASTM G 21
- GREENGUARD Indoor Air Quality
Certified®
- GREENGUARD Children and
SchoolsSM
- NFPA 90A and 90B
In Canada:
- CAN/ULC S102-M88
- CAN/CGSB-51.11-92
Technical Data
Surface Burning
Characteristics
- UL/ULC classified.
- Does not exceed 25 Flame Spread, 50
Smoke Developed when tested in accordance with ASTM E 84, CAN/ULC
S102-M88, NFPA 255 and UL 723.
Temperature Range (ASTM C
411)
Air Velocity (ASTM C
1071)
- Maximum 6000 fpm (1829 mpm).
- Tested to 15,000 fpm (4572 mpm).
Corrosiveness (ASTM C
665)
- Does not accelerate corrosion on steel, copper or
aluminum.
Corrosion (ASTM C
1617)
- The corrosion rate in mils/yr will not exceed that of the 1 ppm
chloride solution.
Water Vapor Sorption (ASTM C
1104)
Water Repellency
Microbial Growth (ASTM C 1338,
G 21, G 22)
- Airstream surface mat facing is treated with an EPA-registered
anti-microbial agent to aid in the prevention of fungal and
bacterial growth.
- Does not promote or support the
growth of mold, fungi or bacteria.
Application &
Specification Guidelines
Storage
- Inside storage is recommended.
Fabrication and
Application
- Fabricate in compliance with the latest edition of NAIMA’s
Fibrous Glass Duct Liner Standard.
- Liner shall be folded and compressed
in the corners of rectangular duct sections or shall be cut and fit
to assure lapped, compressed joints. Longitudinal joints in duct
liner should not occur except at the corner of ducts. Longitudinal
joints in liner shall be coated with adhesive. All damaged areas of
the air stream surface shall be repaired with an adhesive which
conforms to ASTM C 916.
- Liner should be adhered to the duct
with 90% minimum area coverage of an adhesive which conforms to
ASTM C 916.
- Mechanical fasteners should not
compress the insulation more than ⅛" (3 mm), and shall be installed
perpendicular to the duct surface. All fasteners should comply with
the guidelines of NAIMA’s Fibrous Glass Duct Liner Standard and the
Mechanical Fastener’s Standard MF-1-1975.
- Metal nosings shall be securely
installed over transversely oriented liner edges facing the
airstream at fan discharge, at access doors and at any interval of
lined duct preceded by unlined duct. In addition, where velocities
exceed 4000 fpm (1219 mpm), metal nosing small be used on upstream
edges of liner at every transverse joint.
Limitations
- Knauf Sonic XP Duct Liner with ECOSE
Technology should not be used in systems operating at velocities
exceeding 6000 fpm (1829 mpm) or at temperatures above 250°F
(121°C).
Fiber Glass and
Mold
Fiber glass insulation will not
sustain mold growth. However, mold can grow on almost any material
when it becomes wet and contaminated. Carefully inspect any
insulation that has been exposed to water. If it shows any sign of
mold, it must be discarded. If the material is wet but shows no
evidence of mold, it should be dried rapidly and thoroughly. If it
shows signs of facing degradation from wetting, it should be
replaced. Air handling insulation used in the air stream must be
discarded if exposed to water.
Notes
The chemical physical properties of
Knauf Sonic XP Duct Liner with ECOSE Technology represent typical
average values determined in accordance with accepted test methods.
The data is subject to normal manufacturing and testing variations.
The data is supplied as a technical service and is subject to
change without notice. References to numerical flame spread ratings
are not intended to reflect hazards presented by these or any other
materials under actual fire conditions. Check with your Knauf
Insulation sales representative to assure information is
current.

Knauf Sonic XP Duct Liner with ECOSE®
Technology products are certified for indoor air quality by The
GREENGUARD Environmental Institute, to both the GREENGUARD
Certification ProgramSM and the more stringent GREENGUARD For
Children and SchoolsSM Standard. www.
greenguard.org
The GREENGUARD INDOOR AIR QUALITY
CERTIFIED Mark is a registered certification mark used under
license through the GREENGUARD Environmental Institute.
SOUND ABSORPTION COEFFICIENTS, OCTAVE BANDS (ASTM C 423, TYPE A
MOUNTING)
| Density |
Thickness |
125 Hz |
250 Hz |
500 Hz |
1000 Hz |
2000 Hz |
4000 Hz |
NRC |
| 1.5 PCF (24 kg/m3) |
1" (25 mm) |
.18 |
.36 |
.59 |
.86 |
.95 |
.90 |
.70 |
| 1.5 PCF (24 kg/m3) |
1.5" (38 mm) |
.35 |
.51 |
.83 |
.93 |
.97 |
.96 |
.80 |
| 1.5 PCF (24 kg/m3) |
2" (51 mm) |
.34 |
.64 |
.96 |
1.03 |
1.00 |
1.03 |
.90 |
| 2.0 PCF (32 kg/m3) |
.5" (13 mm) |
.09 |
.14 |
.40 |
.60 |
.73 |
.82 |
.45 |
| 2.0 PCF (32 kg/m3) |
1" (25 mm) |
.25 |
.35 |
.69 |
.89 |
.96 |
1.01 |
.70 |
| 2.0 PCF (24 kg/m3) |
1.5" (38 mm) |
.27 |
.55 |
.87 |
.99 |
1.00 |
.98 |
.85 |
FRICTION LOSS (INCHES OF WATER PER 100
FT.)
Air
Velocity
(FPM) |
10" HD |
16" HD |
24" HD |
32" HD |
40" HD |
72" HD |
100" HD |
| 500 |
.054 |
.030 |
.018 |
.012 |
.009 |
.005 |
.003 |
| 600 |
.077 |
.042 |
.025 |
.018 |
.013 |
.007 |
.004 |
| 700 |
.104 |
.057 |
.034 |
.024 |
.018 |
.009 |
.006 |
| 800 |
.134 |
.074 |
.044 |
.031 |
.023 |
.011 |
.008 |
| 900 |
.169 |
.093 |
.056 |
.039 |
.029 |
.014 |
.010 |
| 1000 |
.207 |
.114 |
.068 |
.048 |
.036 |
.018 |
.012 |
| 2000 |
.806 |
.443 |
.266 |
.186 |
.141 |
.069 |
.046 |
| 3000 |
1.797 |
.988 |
.594 |
.415 |
.315 |
.153 |
.103 |
| 4000 |
3.179 |
1.748 |
1.050 |
.734 |
.557 |
.271 |
.181 |
| 5000 |
4.952 |
2.724 |
1.636 |
1.143 |
.867 |
.422 |
.283 |
THERMAL CONDUCTANCE, C AND RESISTANCE, R (ASTM C
177)
|
Density |
Thickness |
C-Value |
C-Value
(SI) |
R-Value |
R-Value (SI) |
| 1.5 PCF (24 kg/m3) |
1" (25 mm) |
.24 |
1.42 |
4.2 |
.74 |
| 1.5 PCF (24 kg/m3) |
1.5" (38 mm) |
.17 |
.97 |
6.0 |
1.06 |
| 1.5 PCF (24 kg/m3) |
2" (51 mm) |
.13 |
.74 |
8.0 |
1.41 |
| 2.0 PCF (32 kg/m3) |
.5" (13 mm) |
.48 |
2.73 |
2.1 |
.37 |
| 2.0 PCF (32 kg/m3) |
1" (25 mm) |
.24 |
1.36 |
4.2 |
.74 |
| 2.0 PCF (32 kg/m3) |
1.5" (38 mm) |
.16 |
.91 |
6.3 |
1.11 |
STANDARD ITEMS
| Density |
Thickness |
Width (34" to 36", no edge-coating) |
Length |
|
1.5 PCF (24 kg/m3)
|
1" (25 mm)
|
35.5", 46.25", 47", 47.5", 48", 56", 56.25", 56.5", 59",
59.25",
59.5", 60", 68", 71"
(902, 1175, 1194, 1207, 1219, 1422, 1428, 1435, 1499, 1505,
1511,1524, 1727, 1803 mm)
|
100' (30.48 m)
|
| 1.5 PCF (24 kg/m3) |
1.5" (38 mm) |
35.5"*, 47", 47.5", 48", 56.25",
59", 59.5"
(902, 1194, 1207, 1219, 1429, 1499, 1511 mm) |
50' (15.24 m) |
| 1.5 PCF (24
kg/m3) |
2" (51 mm) |
34"*, 47", 47.5", 48", 56.25", 59",
59.5", 60"
(902, 1194, 1207, 1219, 1429, 1499, 1511 mm) |
50' (15.24 m) |
| 2.0 PCF (32
kg/m3) |
.5" (13 mm) |
34.25"*, 35.5"*, 47", 47.5", 48",
56.25", 59", 59.5"
(870, 902, 1194, 1207, 1219, 1428, 1499, 1511 mm) |
50' (15.24 m) |
| 2.0 PCF (32
kg/m3) |
1" (25 mm) |
47", 48", 59" (1194, 1219, 1499
mm) |
100' (30.48 m) |