Knauf Duct Liner E-M
Description
Knauf Duct Liner E•M is a flexible, mat-faced insulation made
from inorganic glass fibers bonded by a thermosetting resin with an
encapsulant edge coating. It is faced with a tightly bonded mat to
give the airstream surface a smooth, tough surface, resisting
damage during installation and operation. The encapsulant edge
coating eliminates airstream surface flaring.
Application
Specifically designed as an interior insulation material for
sheet metal ducts used in heating, ventilating, and air
conditioning. Provides an optimum combination of efficient sound
absorption, low thermal conductivity, and minimal airstream surface
friction.
Features
- Low thermal conductivity.
- Fire-resistant, non-corrosive, durable, and resilient.
- Tough, tightly bonded mat facing.
- Excellent sound absorption.
Benefits
- Energy conservation.
- Better temperature control.
- Lower operating costs.
- Greatly reduces noise from fans and mechanical equipment, as
well as noise from cross-talk and air movement.
- Withstands damage from normal handling and shop abuse.
- If necessary, can be cleaned in accordance with NAIMA's
“Cleaning Fibrous Glass Insulated Air Duct Systems Recommended
Practices.”
Specification Compliance
In U.S.:
- ASTM C 1071; Type I*
- ASTM D 5116
- ASTM G 21, G 22
- GREENGUARD Environmental Institute™
- California Title 24
(1.5 PCF, 1" and above)
- NFPA 90A and 90B
- State of Alaska IAQ Specifications
- State of Washington IAQ Specifications
*Replaces HH-I-545B; Type I
In Canada:
- CAN/ULC S102-M88
- CAN/CGSB 51.11-92
Technical Data
Surface Burning Characteristics
- UL/ULC listed.
- Does not exceed 25 Flame Spread, 50 Smoke Developed when tested
in accordance with ASTM E 84, CAN/ULC S102-M88, NFPA 255 and UL
723.
Temperature Range (ASTM C 411)
Air Velocity (ASTM C 1071)
- Maximum 6000 fpm (1829 mpm).
- Tested to 15,000 fpm (4572 mpm).
Water Vapor Sorption (ASTM C 1104)
Microbial Growth (ASTM C 1338, G 21, G 22)
- Airstream surface mat facing is treated with an EPA-registered
anti-microbial agent to aid in the prevention of fungal and
bacterial growth.
- Does not promote or support the growth of mold, fungi, or
bacteria.
Application and Specification Guidelines
Storage
- Inside storage is recommended.
Fabrication and Application
- Fabricate in compliance with the latest edition of NAIMA's
Fibrous Glass Duct Liner Standard.
- Liner shall be folded and compressed in the corners of
rectangular duct sections or shall be cut and fit to assure lapped,
compressed joints. Longitudinal joints in duct liner should not
occur except at the corners of the duct. Longitudinal joints in
liner shall be coated with adhesive. All damaged areas of the air
stream surface shall be repaired with an adhesive that conforms to
ASTM C 916.
- Liner should be adhered to the duct with 90% minimum area
coverage of an adhesive taht conforms to ASTM C 916.
- Mechanical fasteners shall be located with respect to the
interior duct dimensions, regardless of air flow direction.
- Mechanical fasteners should not compress the insulation more
than 1/8" (3 mm), and shall be installed perpendicular
to the duct surface. All fasteners should comply with the
guidelines of NAIMA's Fibrous Glass Duct Liner Standard.
- Metal nosings shall be securely installed over transversely
oriented liner edges facing the air stream at fan discharge, at
access doors, and at any interval of lined duct preceeded by
unlined duct. In addition, where velocities exceed 4000 fpm (1219
mpm), metal nosing shall be used on upstream edges of liner at
every transverse joint.
Limitations
- Knauf Duct Liner E•M should not be used in systems operating at
velocities exceeding 6000 fpm (1829 mpm) or at temperatures above
250°F (121°C).
Notes
The chemical and physical properties of Knauf Duct Liner E•M
represent typical average values determined in accordance with
accepted test methods. The data is subject to normal manufacturing
variations. The data is supplied as a technical service and is
subject to change without notice. References to numerical flame
spread ratings are not intended to reflect hazards presented by
these or any other materials under actual fire conditions. Check
with your Knauf regional office to assure information is
current.

Knauf Duct Liner E•M products are certified for indoor air quality
by The GREENGUARD Environmental Institute™, a global, non-profit
organization, providing the world’s leading guide to certified low
emitting interior products and building materials through
independent, indoor air quality laboratory testing.
http://www.greenguard.org/
SOUND ABSORPTION COEFFICIENTS,
1/3 OCTAVE BANDS (ASTM C 423, TYPE A MOUNTING)
| Density |
Thickness |
125 Hz |
250 Hz |
500 Hz |
1000 Hz |
2000 Hz |
4000 Hz |
NRC |
| 1.5 PCF (24 kg/m3) |
1" (25 mm) |
.18 |
.36 |
.59 |
.86 |
.95 |
.90 |
.70 |
| 1.5 PCF (24 kg/m3) |
1.5" (38 mm) |
.35 |
.51 |
.83 |
.93 |
.97 |
.96 |
.80 |
| 1.5 PCF (24 kg/m3) |
2" (51 mm) |
.34 |
.64 |
.96 |
1.03 |
1.00 |
1.03 |
.90 |
| 2.0 PCF (32 kg/m3) |
.5" (13 mm) |
.09 |
.14 |
.40 |
.60 |
.73 |
.82 |
.45 |
| 2.0 PCF (32 kg/m3) |
1" (25 mm) |
.25 |
.35 |
.69 |
.89 |
.96 |
1.01 |
.70 |
| 2.0 PCF (32 kg/m3) |
1.5" (38 mm) |
.27 |
.55 |
.87 |
.99 |
1.00 |
.98 |
.85 |
FRICTION LOSS (INCHES OF WATER PER
100 FT.)
Air
Velocity
(FPM) |
10"
HD |
16"
HD |
24"
HD |
32"
HD |
40"
HD |
72"
HD |
100"
HD |
| 500 |
.054 |
.030 |
.018 |
.012 |
.009 |
.005 |
.003 |
| 600 |
.077 |
.042 |
.025 |
.018 |
.013 |
.007 |
.004 |
| 700 |
.104 |
.057 |
.034 |
.024 |
.018 |
.009 |
.006 |
| 800 |
.134 |
.074 |
.044 |
.031 |
.023 |
.011 |
.008 |
| 900 |
.169 |
.093 |
.056 |
.039 |
.029 |
.014 |
.010 |
| 1000 |
.207 |
.114 |
.068 |
.048 |
.036 |
.018 |
.012 |
| 2000 |
.806 |
.443 |
.266 |
.186 |
.141 |
.069 |
.046 |
| 3000 |
1.797 |
.988 |
.594 |
.415 |
.315 |
.153 |
.103 |
| 4000 |
3.179 |
1.748 |
1.050 |
.734 |
.557 |
.271 |
.181 |
| 5000 |
4.952 |
2.724 |
1.636 |
1.143 |
.867 |
.422 |
.283 |
THERMAL CONDUCTANCE, C AND RESISTANCE, R (ASTM C
177)
| Density |
Thickness |
C-Value |
C-Value
(SI) |
R-Value |
R-Value
(SI) |
| 1.5 PCF (24 kg/m3) |
1" (25 mm) |
.24 |
1.36 |
4.2 |
.74 |
| 1.5 PCF (24 kg/m3) |
1.5" (38 mm) |
.17 |
.97 |
6.0 |
1.06 |
| 1.5 PCF (24 kg/m3) |
2" (51 mm) |
.13 |
.74 |
8.0 |
1.41 |
| 2.0 PCF (32 kg/m3) |
.5" (13 mm) |
.48 |
2.73 |
2.1 |
.37 |
| 2.0 PCF (32 kg/m3) |
1" (25 mm) |
.24 |
1.36 |
4.2 |
.74 |
| 2.0 PCF (32 kg/m3) |
1.5" (38 mm) |
.16 |
.91 |
6.3 |
1.11 |
STANDARD ITEMS
| Density |
Thickness |
Width (34" to 36", no
edge-coating) |
Length |
|
1.5 PCF (24 kg/m3)
|
1" (25 mm)
|
35.5", 46.25", 47", 47.5", 48",
56",
56.25", 56.5", 59", 59.5", 60"
(902, 1175, 1194, 1207, 1219, 1422,
1428, 1435, 1499, 1511, 1524 mm)
|
100' (30.48 m)
|
| 1.5 PCF (24 kg/m3) |
1" (25 mm) |
47"
(1194 mm) |
50' (15.24 m) |
| 1.5 PCF (24 kg/m3) |
1.5" (38 mm) |
47", 48"
(1194, 1219 mm) |
50' (15.24 m) |
| 1.5 PCF (24 kg/m3) |
2" (51 mm) |
47", 48"
(1194, 1219 mm) |
50' (15.24 m) |
| 2.0 PCF (32 kg/m3) |
.5" (13 mm) |
35.5", 47", 47.5", 48", 59",
59.5"
(902, 1194, 1207, 1219, 1499, 1511 mm) |
100' (30.48 m) |
| 2.0 PCF (32 kg/m3) |
1" (25 mm) |
47.5", 48"
(1207, 1219 mm) |
50' (15.24 m) |