Knauf Duct Liner E-M

Knauf Duct Liner E•M is a flexible, mat-faced insulation made from inorganic glass fibers bonded by a thermosetting resin with an encapsulant edge coating. It is faced with a tightly bonded mat to give the airstream surface a smooth, tough surface, resisting damage during installation and operation. The encapsulant edge coating eliminates airstream surface flaring.

Application

Specifically designed as an interior insulation material for sheet metal ducts used in heating, ventilating, and air conditioning. Provides an optimum combination of efficient sound absorption, low thermal conductivity, and minimal airstream surface friction.

Features

  • Low thermal conductivity.
  • Fire-resistant, non-corrosive, durable, and resilient.
  • Tough, tightly bonded mat facing.
  • Excellent sound absorption.

Benefits

  • Energy conservation.
  • Better temperature control.
  • Lower operating costs.
  • Greatly reduces noise from fans and mechanical equipment, as well as noise from cross-talk and air movement.
  • Withstands damage from normal handling and shop abuse.
  • If necessary, can be cleaned in accordance with NAIMA's “Cleaning Fibrous Glass Insulated Air Duct Systems Recommended Practices.”

Specification Compliance

In U.S.:

  • ASTM C 1071; Type I*
  • ASTM D 5116
  • ASTM G 21, G 22
  • GREENGUARD Environmental Institute™
  • California Title 24
    (1.5 PCF, 1" and above)
  • NFPA 90A and 90B
  • State of Alaska IAQ Specifications
  • State of Washington IAQ Specifications
    *Replaces HH-I-545B; Type I

In Canada:

  • CAN/ULC S102-M88
  • CAN/CGSB 51.11-92

Technical Data

Surface Burning Characteristics

  • UL/ULC listed.
  • Does not exceed 25 Flame Spread, 50 Smoke Developed when tested in accordance with ASTM E 84, CAN/ULC S102-M88, NFPA 255 and UL 723.

Temperature Range (ASTM C 411)

  • Up to 250°F (121°C).

Air Velocity (ASTM C 1071)

  • Maximum 6000 fpm (1829 mpm).
  • Tested to 15,000 fpm (4572 mpm).

Water Vapor Sorption (ASTM C 1104)

  • Less than 3% by weight.

Microbial Growth (ASTM C 1338, G 21, G 22)

  • Airstream surface mat facing is treated with an EPA-registered anti-microbial agent to aid in the prevention of fungal and bacterial growth.
  • Does not promote or support the growth of mold, fungi, or bacteria.

Application and Specification Guidelines

Storage

  • Inside storage is recommended.

Fabrication and Application

  • Fabricate in compliance with the latest edition of NAIMA's Fibrous Glass Duct Liner Standard.
  • Liner shall be folded and compressed in the corners of rectangular duct sections or shall be cut and fit to assure lapped, compressed joints. Longitudinal joints in duct liner should not occur except at the corners of the duct. Longitudinal joints in liner shall be coated with adhesive. All damaged areas of the air stream surface shall be repaired with an adhesive that conforms to ASTM C 916.
  • Liner should be adhered to the duct with 90% minimum area coverage of an adhesive taht conforms to ASTM C 916.
  • Mechanical fasteners shall be located with respect to the interior duct dimensions, regardless of air flow direction.
  • Mechanical fasteners should not compress the insulation more than 1/8" (3 mm), and shall be installed perpendicular to the duct surface. All fasteners should comply with the guidelines of NAIMA's Fibrous Glass Duct Liner Standard.
  • Metal nosings shall be securely installed over transversely oriented liner edges facing the air stream at fan discharge, at access doors, and at any interval of lined duct preceeded by unlined duct. In addition, where velocities exceed 4000 fpm (1219 mpm), metal nosing shall be used on upstream edges of liner at every transverse joint.

Limitations

  • Knauf Duct Liner E•M should not be used in systems operating at velocities exceeding 6000 fpm (1829 mpm) or at temperatures above 250°F (121°C).

Notes

The chemical and physical properties of Knauf Duct Liner E•M represent typical average values determined in accordance with accepted test methods. The data is subject to normal manufacturing variations. The data is supplied as a technical service and is subject to change without notice. References to numerical flame spread ratings are not intended to reflect hazards presented by these or any other materials under actual fire conditions. Check with your Knauf regional office to assure information is current.
 

Greenguard Logo

Knauf Duct Liner E•M products are certified for indoor air quality by The GREENGUARD Environmental Institute™, a global, non-profit organization, providing the world’s leading guide to certified low emitting interior products and building materials through independent, indoor air quality laboratory testing. http://www.greenguard.org/
 
 
SOUND ABSORPTION COEFFICIENTS, 1/3 OCTAVE BANDS (ASTM C 423, TYPE A MOUNTING)
Density Thickness 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz NRC
1.5 PCF (24 kg/m3) 1" (25 mm) .18 .36 .59 .86 .95 .90 .70
1.5 PCF (24 kg/m3) 1.5" (38 mm) .35 .51 .83 .93 .97 .96 .80
1.5 PCF (24 kg/m3) 2" (51 mm) .34 .64 .96 1.03 1.00 1.03 .90
2.0 PCF (32 kg/m3) .5" (13 mm) .09 .14 .40 .60 .73 .82 .45
2.0 PCF (32 kg/m3) 1" (25 mm) .25 .35 .69 .89 .96 1.01 .70
2.0 PCF (32 kg/m3) 1.5" (38 mm) .27 .55 .87 .99 1.00 .98 .85
 
FRICTION LOSS (INCHES OF WATER PER 100 FT.)
Air Velocity
(FPM)
10" HD 16" HD 24" HD 32" HD 40" HD 72" HD 100" HD
500 .054 .030 .018 .012 .009 .005 .003
600 .077 .042 .025 .018 .013 .007 .004
700 .104 .057 .034 .024 .018 .009 .006
800 .134 .074 .044 .031 .023 .011 .008
900 .169 .093 .056 .039 .029 .014 .010
1000 .207 .114 .068 .048 .036 .018 .012
2000 .806 .443 .266 .186 .141 .069 .046
3000 1.797 .988 .594 .415 .315 .153 .103
4000 3.179 1.748 1.050 .734 .557 .271 .181
5000 4.952 2.724 1.636 1.143 .867 .422 .283
 
THERMAL CONDUCTANCE, C AND RESISTANCE, R (ASTM C 177)
Density Thickness C-Value C-Value (SI) R-Value R-Value (SI)
1.5 PCF (24 kg/m3) 1" (25 mm) .24 1.36 4.2 .74
1.5 PCF (24 kg/m3) 1.5" (38 mm) .17 .97 6.0 1.06
1.5 PCF (24 kg/m3) 2" (51 mm) .13 .74 8.0 1.41
2.0 PCF (32 kg/m3) .5" (13 mm) .48 2.73 2.1 .37
2.0 PCF (32 kg/m3) 1" (25 mm) .24 1.36 4.2 .74
2.0 PCF (32 kg/m3) 1.5" (38 mm) .16 .91 6.3 1.11
 
STANDARD ITEMS
Density Thickness Width (34" to 36", no edge-coating) Length

1.5 PCF (24 kg/m3)

1" (25 mm)

35.5", 46.25", 47", 47.5", 48", 56",

56.25", 56.5", 59", 59.5", 60"
(902, 1175, 1194, 1207, 1219, 1422,

1428, 1435, 1499, 1511, 1524 mm)

100' (30.48 m)

1.5 PCF (24 kg/m3) 1" (25 mm) 47"
(1194 mm)
50' (15.24 m)
1.5 PCF (24 kg/m3) 1.5" (38 mm) 47", 48"
(1194, 1219 mm)
50' (15.24 m)
1.5 PCF (24 kg/m3) 2" (51 mm) 47", 48"
(1194, 1219 mm)
50' (15.24 m)
2.0 PCF (32 kg/m3) .5" (13 mm) 35.5", 47", 47.5", 48", 59", 59.5"
(902, 1194, 1207, 1219, 1499, 1511 mm)
100' (30.48 m)
2.0 PCF (32 kg/m3) 1" (25 mm) 47.5", 48"
(1207, 1219 mm)
50' (15.24 m)

Website Options

Language Links To Other Country Sites
Search

Latest News