Knauf Air Duct Board-M
Description
Knauf Air Duct Board-M with Hydroshield Technology is a
resin-bonded fiber glass formed into rigid, rectangular boards
faced on one side with a fire-resistant foil-scrim-kraft (FSK)
vapor retarder, and its airstream surface is faced with a tightly
bonded, non-woven mat. Available in EI-475 or EI-800, with butt
edge or factory-applied shiplap edge, it offers excellent thermal
and acoustical performance.
Hydroshield Technology helps keep moisture from penetrating the
airstream surface of the product, reducing the opportunity for
water to penetrate the board. It is important to note that liquid
water should be kept out of any HVAC system regardless of the
materials employed. Hydroshield Technology is a product feature
that enhances the water hold-out properties of the airstream
surface of the product; however, it does not eliminate the
opportunity for moisture to penetrate the board.
Application
Knauf Air Duct Board-M is designed for commercial and
residential air handling installations for cooling, heating, or
dual-temperature service where good temperature control, noise
absorption, and abuse resistance are required.
Features
- Hydroshield Technology mat facing.
- Low thermal conductivity of 0.23 at 75°F (24°C) mean
temperature.
- Low installed cost, insulated duct system.
- Excellent acoustical characteristics.
- Assured insulation thickness, shiplap joints, and FSK vapor
retarder.
- If necessary, can be cleaned in accordance with NAIMA's
“Cleaning Fibrous Glass Insulated Air Duct Systems Recommended
Practices.”
- Knauf Air Duct Board systems meet the fire and smoke safety
regulations of most federal, state, and local building codes.
Benefits
- Moisture hold out properties that significantly reduce the
opportunity for moisture to penetrate the air stream surface.
- Airstream surface is significantly more resistant to abuse than
coated duct board products.
- Does not support growth of mold, fungi, or bacteria.
- Airstream surface is 20% less porous to air than coated duct
board products.
- Fabrication in shop environment lowers field installation
time.
- One craft required to fabricate and install system.
- Minimum capital investment for fabrication equipment.
- Portability allows for assembly or fabrication at job
site.
- Lower installation cost than with duct wrap and duct
liner.
- Quiet, efficient air delivery.
- Reduces noise generated by air turbulence and mechanical
equipment.
- Eliminates “booming” and “cracking” sounds caused by sheet
metal duct contraction and expansion.
- Condensation control.
- Strong thermal performance.
- Code compliance.
Specification Compliance
In U.S.:
- ASTM C 1136; Type II (FSK facing)
- ASTM D 5116
- ASTM G 21, G 22
- BOCA
- CABO
- California Title 24
- Corps of Engineers Guide Specifications
- ICBO
- International Mechanical Code
- NFPA 90A and 90B
- SBCCI
- State of Alaska IAQ Specifications
- State of Washington IAQ Specifications
- UL 181; Class 1
In Canada:
- CAN/ULC S102-M88
- CAN/CGSB 51-GP-52M (facing)
- CAN/CGSB 51.10-92
- ULC Issue 869C; Class 1
Technical Data
Surface Burning Characteristics
- UL/ULC listed.
- Does not exceed 25 Flame Spread, 50 Smoke Developed when tested
in accordance with ASTM E 84, CAN/ULC S102-M88, NFPA 255, and UL
723.
Flexural Rigidity
- Available in two stiffness values: EI-475 and EI-800.
- Flexural rigidity (EI) is the product of Young's modulus of
elasticity (E) and moment of inertia (I) as determined in
accordance with NAIMA AHS-100-74.
Service Temperature (ASTM C 411)
Air Velocity (UL 181)
- Maximum 5000 fpm (1524 mpm).
- Tested to 12,500 fpm (3810 mpm).
Internal Static Pressure (UL 181)
- Maximum ±2" water (498 pascals [Pa]).
Water Vapor Permeance (ASTM E 96)
Water Vapor Sorption (ASTM C 1104)
Microbial Growth (ASTM G 21, G 22, UL 181)
- Does not promote or support the growth of mold, fungi, or
bacteria.
- Airstream surface mat-facing is treated with an EPA-registered
anti-microbial agent to aid in the prevention of fungal and
bacterial growth.
Airstream Surface Abuse (K-103)
- Average of 370 seconds to surface penetration.
Application and Specification Guidelines
Storage
- Protect stored duct board from water damage, construction
damage, and other abuse.
- If stored outside, proper protection from weather conditions
should be provided.
Application
- Duct shall be fabricated and installed in strict accordance
with NAIMA's “Fibrous Glass Duct Construction Standard,”
“Residential Standard,” “11/2"
Fabrication Manual,” or Knauf Insulation “Air Duct Fabrication
Manual,” and in accordance with the conditions of UL 181 listing.
Duct systems shall have all transverse joints, longitudinal seams,
and duct wall penetrations sealed using 3" (76 mm) wide glass
fabric and mastic, 2" (51 mm) minimum width heat-sealable tape, or
2" (51 mm) minimum width pressure-sensitive tape with acrylic
adhesive. Rubber based adhesives are not approved.
- Only UL 181-A listed and labeled products shall be used for
closure systems. A listing of approved closure products is
available from you local Knauf sales representative.
PRESSURE-SENSITIVE TAPES: Only those tapes listed under and
imprinted with designation UL 181 A-P and registered with UL.
HEAT-SEALABLE TAPES: Only those tapes listed under and imprinted
with designation UL 181 A-H and registered with UL.
MASTICS: Mastic systems listed and registered with UL and carrying
the designation UL 181 A-M used in conjunction with a 3" (76 mm)
wide glass fabric.
Procedures
Closure
If the closure system used is not one of the approved systems
described above, and if application is not in accordance with
stated procedures, Knauf Insulation assumes no liability for duct
system performance. Use of a non-UL registered and listed closure
voids the UL 181 Class 1 rating as well as Knauf's product
performance warranties.
Reinforcements
Duct sections shall be additionally reinforced where
necessary, according to Knauf Insulation and NAIMA standards.
Ductwork shall be supported as required on straight runs, at all
turns, and at transitions to maintain proper alignment. Hangers and
supports shall be in strict accordance with Knauf Insulation and
NAIMA standards.
Notes
When used in accordance with NAIMA and Knauf Insulation
application instructions, the closure systems described herein meet
UL 181 requirements, and the resulting system carries a Class 1 Air
Duct rating.
This data sheet is not intended to be a design or fabrication
manual. For specific details and recommendations on fabrication,
reinforcement, hanging, and other details, refer to the latest
edition of the NAIMA “Fibrous Glass Duct Construction Standard,”
“Residential Standard,” “11/2"
Fabrication Manual,” or Knauf Insulation “Air Duct Fabrication
Manual.”
Application and installation procedure is at the discretion of
and is the responsibility of the Design Engineer to meet specific
job requirements.
The chemical and physical properties of Knauf Air Duct Board-M
with Hydroshield™ Technology represent typical average values
determined in accordance with accepted test methods. The data is
subject to normal manufacturing variations. The data is supplied as
a technical service and is subject to change without notice.
References to numerical flame spread ratings are not intended to
reflect hazards presented by these or any other materials under
actual fire conditions. Check with your Knauf regional office to
assure information is current.
ACOUSTICAL INSERTION LOSS (DB/10 LF),
1/3 OCTAVE BANDS (ASTM E 477)
| Thickness |
Duct Dimension |
63
Hz |
125
Hz |
250
Hz |
500
Hz |
1000
Hz |
2000
Hz |
4000
Hz |
8000
Hz |
|
1"
(25 mm)
|
12" x 12"
(305 mm x 305 mm)
|
1.7 |
13.5 |
13.8 |
27.3 |
38.3 |
41.3 |
24.7 |
19.1 |
|
11/2"
(38 mm)
|
12" x 12"
(305 mm x 305 mm)
|
1.7 |
12.0 |
20.9 |
26.0 |
46.5 |
38.9 |
24.7 |
20.0 |
|
1"
(25 mm)
|
12" x 24"
(305 mm x 610 mm)
|
.6 |
8.9 |
10.2 |
21.0 |
39.0 |
29.7 |
18.9 |
15.7 |
|
11/2"
(38 mm)
|
12" x 24"
(305 mm x 610 mm)
|
1.7 |
8.9 |
15.9 |
25.2 |
45.8 |
28.2 |
19.1 |
16.3 |
FRICTION LOSS (INCHES OF
WATER PER 100 FT.)
Air Velocity
(FPM) |
10" HD |
16" HD |
24" HD |
32" HD |
40"
HD |
72"
HD |
100"
HD |
| 500 |
.045 |
.025 |
.015 |
.011 |
.008 |
.004 |
.003 |
| 600 |
.064 |
.036 |
.022 |
.015 |
.012 |
.006 |
.004 |
| 700 |
.085 |
.047 |
.029 |
.020 |
.015 |
.008 |
.005 |
| 800 |
.109 |
.061 |
.037 |
.026 |
.020 |
.010 |
.007 |
| 900 |
.136 |
.076 |
.046 |
.033 |
.025 |
.012 |
.008 |
| 1000 |
.166 |
.093 |
.056 |
.040 |
.030 |
.015 |
.010 |
| 2000 |
.624 |
.349 |
.213 |
.150 |
.114 |
.056 |
.038 |
| 3000 |
1.369 |
.766 |
.467 |
.329 |
.251 |
.124 |
.084 |
| 4000 |
2.400 |
1.344 |
.818 |
.577 |
.441 |
.218 |
.147 |
| 5000 |
3.719 |
2.082 |
1.268 |
.894 |
.683 |
.337 |
.228 |
THERMAL RESISTANCE, R (ASTM C 518)
@ 75°F (24°C) MEAN TEMPERATURE
| Thickness |
R-Value |
R-Value (SI) |
| 1" (25 mm) |
4.3 |
.76 |
| 11/2" (38 mm) |
6.5 |
1.14 |
| 2" (51 mm) |
8.7 |
1.53 |
THERMAL CONDUCTIVITY, K (ASTM C 177)
@ 75°F (24°C) MEAN TEMPERATURE
| |
k |
k (SI) |
| Knauf Air Duct Type EI-475 and EI-800 |
.23 |
.033 |
FORMS AVAILABLE
| Thickness |
Type |
Size |
Edge |
Pieces/Carton |
1"
(25 mm) |
EI-475, EI-800 |
48" x 96"
(1219 mm x 2438 mm) |
Butt, Shiplap |
8 |
1"
(25 mm) |
EI-475, EI-800 |
48" x 120"
(1219 mm x 3048 mm) |
Butt, Shiplap |
6 |
11/2"
(38 mm) |
EI-800 |
48" x 120"
(1219 mm x 3048 mm) |
Butt, Shiplap |
4 |
2"
(51 mm) |
EI-800 |
48" x 120"
(1219 mm x 3048 mm) |
Butt |
3 |
*Other lengths on made-to-order
basis. **Palletized packaging on
request.