Knauf Eclipse Air Duct Board
Description
Knauf EclipseTM Air Duct Board is a resin-bonded
fiber glass formed into rigid, rectangular boards faced on one side
with a fire-resistant foil-scrim-kraft (FSK) vapor retarder and a
lightweight black fiber glass mat on the airstream surface.
Available in EI-475 or EI-800. Both types
are available with a butt edge or a factory-molded
shiplap edge. The airstream surface of Knauf Eclipse Air Duct Board
is treated with an EPA registered, antimicrobial agent that
prevents growth of mold, fungus or bacteria in accordance with ASTM
C 1071, G21 and G22.
Application
Knauf Eclipse Air Duct Board is designed for commercial
and residential air handling installations for cooling, heating, or
dual-temperature service where good temperature control and noise
absorption are required.
Features
- Low thermal conductivity of 0.23 at 75°F (24°C) mean
temperature.
- Low installed cost, insulated duct system.
- Excellent acoustical characteristics.
- Non-woven all-glass mat facing on the airstream surface.
- Assured insulation thickness, shiplap joints, and FSK vapor
retarder.
- If necessary, can be cleaned in accordance with NAIMA's
“Cleaning Fibrous Glass Insulated Air Duct Systems Recommended
Practices.”
- Knauf Eclipse Air Duct Board systems meet the fire and smoke
safety regulations of most federal, state, and local building
codes.
- Fabrication in shop or on jobsite.
- Dark black glass mat airstream surface.
Benefits
- Fabrication in shop environment lowers field installation
time.
- One craft required to fabricate and install system.
- Minimum capital investment for fabrication equipment.
- Portability allows for assembly or fabrication at job
site.
- Black mat facing ensures a smoother airstream surface for
a cleaner cut and added durability.
- Lower installation cost than with duct wrap and duct liner with
sheet metal.
- Quiet, efficient air delivery.
- Reduces noise generated by air turbulence and mechanical
equipment.
- Eliminates “booming” and “cracking” sounds caused by sheet
metal duct contraction and expansion.
- Condensation control.
- Strong thermal performance.
- Code compliance.
Specification Compliance
In U.S.:
- ASTM C 1136; Type II (FSK facing)
- ASTM D 5116
- ASTM G 21, G 22
- GREENGUARDTM Certification
- BOCA
- CABO
- California Title 24
- Corps of Engineers Guide Specifications
- ICBO
- International Mechanical Code
- NFPA 90A and 90B
- SBCCI
- UL 181; Class 1
In Canada:
- CAN/ULC S102-M88
- CAN/CGSB 51-GP-52M (facing)
- CAN/CGSB 51.10-92
- ULC Issue 869C; Class 1
Technical Data
- UL/ULC listed.
- Does not exceed 25 Flame Spread, 50 Smoke Developed when tested
in accordance with ASTM E 84, CAN/ULC S102-M88, NFPA 255, and UL
723.
Flexural Rigidity
- Available in two stiffness values: EI-475 and EI-800.
- Flexural rigidity (EI) is the product of Young's modulus of
elasticity (E) and moment of inertia (I) as determined in
accordance with NAIMA AHS-100-74.
Service Temperature (ASTM C 411)
Air Velocity (UL 181)
- Maximum 5000 fpm (1524 mpm).
- Tested to 12,500 fpm (3810 mpm).
Internal Static Pressure (UL 181)
- Maximum ±2" water (498 pascals [Pa]).
Water Vapor Permeance (ASTM E 96)
Water Vapor Sorption (ASTM C 1104)
Microbial Growth (ASTM G 21, G 22, UL 181)
- Does not promote or support the growth of mold, fungi, or
bacteria.
Application and Specification Guidelines
Storage
- Protect stored duct board from water damage, construction
damage, and other abuse.
- If stored outside, proper protection from weather conditions
should be provided.
Application
- Duct shall be fabricated and installed in strict accordance
with NAIMA's “Fibrous Glass Duct Construction Standard,”
“Residential Standard,” “11/2" Fabrication Manual,” or
Knauf Insulation “Air Duct Fabrication Manual,” and in accordance
with the conditions of UL 181 listing. Duct systems shall have all
transverse joints, longitudinal seams, and duct wall penetrations
sealed using 3" (76 mm) wide glass fabric and mastic, 2" (51 mm)
minimum width heat-sealable tape, or 2" (51 mm) minimum width
pressure-sensitive tape with acrylic adhesive. Rubber based
adhesives are not approved.
- Only UL 181-A listed and labeled products shall be used for
closure systems. A listing of approved closure products is
available from your local Knauf sales representative.
PRESSURE-SENSITIVE TAPES: Only those tapes listed under and
imprinted with designation UL 181 A-P and registered with UL.
HEAT-SEALABLE TAPES: Only those tapes listed under and imprinted
with designation UL 181 A-H and registered with UL.
MASTICS: Mastic systems listed and registered with UL and carrying
the designation UL 181 A-M used in conjunction with a 3" (76 mm)
wide glass fabric.
Procedures
Closure
If the closure system used is not one of the approved systems
described above, and if application is not in accordance with
stated procedures, Knauf Insulation assumes no liability for duct
system performance. Use of a non-UL registered and listed closure
voids the UL 181 Class 1 rating as well as Knauf's product
performance warranties.
Reinforcements
Duct sections shall be additionally reinforced where
necessary, according to Knauf Insulation and NAIMA standards.
Ductwork shall be supported as required on straight runs, at all
turns, and at transitions to maintain proper alignment. Hangers and
supports shall be in strict accordance with Knauf Insulation and
NAIMA standards.
Notes
When used in accordance with NAIMA and Knauf Insulation
application instructions, the closure systems described herein meet
UL 181 requirements, and the resulting system carries a Class 1 Air
Duct rating.
This data sheet is not intended to be a design or fabrication
manual. For specific details and recommendations on fabrication,
reinforcement, hanging, and other details, refer to the latest
edition of the NAIMA “Fibrous Glass Duct Construction Standard,”
“Residential Standard,” “11/2" Fabrication Manual,” or
Knauf Insulation “Air Duct Fabrication Manual.”
Application and installation procedure is at the discretion of
and is the responsibility of the Design Engineer to meet specific
job requirements.
The chemical and physical properties of Knauf Air Duct
Board-AGM represent typical average values determined in accordance
with accepted test methods. The data is subject to normal
manufacturing variations. The data is supplied as a technical
service and is subject to change without notice. References to
numerical flame spread ratings are not intended to reflect hazards
presented by these or any other materials under actual fire
conditions. Check with your Knauf regional office to assure
information is current.
SOUND ABSORPTION COEFFICIENTS,
1/3 OCTAVE BANDS (ASTM C 423, TYPE
A MOUNTING)
| Type |
|
125 Hz |
250 Hz |
500 Hz |
1000 Hz |
2000 Hz |
4000 Hz |
NRC |
| EI-475 |
1" (25 mm) |
.03 |
.25 |
.62 |
.89 |
1.03 |
.97 |
.70 |
| EI-800 |
11/2" (38 mm) |
.02 |
.44 |
.96 |
1.17 |
1.16 |
1.12 |
.95 |
| EI-800 |
2" (51 mm) |
.19 |
.64 |
1.08 |
1.13 |
1.06 |
1.06 |
1.00 |
FRICTION LOSS (INCHES OF
WATER PER 100 FT.)
| Air Velocity (FPM) |
10" HD |
16" HD |
24" HD |
32" HD |
40" HD |
72" HD |
100" HD |
| 500 |
.056 |
.031 |
.018 |
.013 |
.010 |
.005 |
.003 |
| 600 |
.080 |
.044 |
.026 |
.018 |
.014 |
.007 |
.004 |
| 700 |
.108 |
.059 |
.035 |
.025 |
.019 |
.009 |
.006 |
| 800 |
.140 |
.077 |
.046 |
.032 |
.024 |
.012 |
.008 |
| 900 |
.176 |
.096 |
.058 |
.040 |
.031 |
.015 |
.010 |
| 1000 |
.216 |
.118 |
.071 |
.050 |
.038 |
.018 |
.012 |
| 2000 |
.845 |
.463 |
.278 |
.194 |
.147 |
.071 |
.048 |
| 3000 |
1.887 |
1.034 |
.620 |
.432 |
.328 |
.159 |
.106 |
| 4000 |
3.340 |
1.831 |
1.097 |
.765 |
.580 |
.281 |
.188 |
| 5000 |
5.206 |
2.854 |
1.710 |
1.193 |
.904 |
.438 |
.293 |
THERMAL RESISTANCE, R (ASTM C 518)
@ 75°F (24°C) MEAN TEMPERATURE
| Thickness |
R-Value |
R-Value (SI) |
| 1" (25 mm) |
4.3 |
.76 |
| 11/2" (38 mm) |
6.5 |
1.14 |
| 2" (51 mm) |
8.7 |
1.53 |
THERMAL CONDUCTIVITY, K
(ASTM C 177) @ 75°F (24°C) MEAN
TEMPERATURE
| |
k |
k (SI) |
| Knauf Air Duct Type EI-475 and EI 800 |
.23 |
.033 |
FORMS AVAILABLE
| Thickness |
Type |
Size* |
Edge |
Pieces/Carton** |
1"
(25 mm) |
EI-475, EI-800 |
48" x 96"
(1219 mm x 2438 mm) |
Butt, Shiplap |
8 |
1"
(25 mm) |
EI-475, EI-800 |
48" x 120"
(1219 mm x 3048 mm) |
Butt, Shiplap |
6 |
11/2"
(38 mm) |
EI-800 |
48" x 120"
(1219 mm x 3048 mm) |
Butt, Shiplap |
4 |
2"
(51 mm) |
EI-800 |
48" x 120"
(1219 mm x 3048 mm) |
Butt |
3 |
*Other lengths on
made-to-order basis. **Palletized packaging on